TB318 Rev2 – Setup Parameters for Automation Direct GS20 Inverter
Objective
The purpose of this document is to provide the information needed to correctly setup the Automation Direct GS20 inverter for
a Centroid CNC control
Wiring Terminals
Terminal Meaning Typical wire color
R/L1 S/L2 T/L3 Incoming 3 phase AC power BLK or BLK/RED/WHT
U/T1 V/T2 W/T3 3 phase power out to motor BLK or BLK/RED/WHT
B1 B2 Braking resistor BLK or WHT
FWD Run Forward WHT
REV Run Reverse BLK
DI4 Reset not default must set P2 04 = 5 GRN
DCM Input Sequence Common BLU
AI1 Analog frequency reference 0 10V BRN
ACM Analog common VIO plus WHT/BLK
AO1 Analog output WHT/RED
R1C Fault normally closed ORG
DO1 Zero speed set P2 16 = 6 WHT/BRN or TAN
R1 and DOC DC common 0VDC YEL
+24V STO1 STO2 Safe Torque Off function Various
How to change a parameter
For this example we will set P02 04 = 5
1 Press MENU as needed to show the parameter screen typically "H 0 00"
2 Press ENTER to show the parameter group e g "00"
3 Press the Up Arrow as needed to select the desired group e g twice for 02
4 Press ENTER to show the parameter number e g "0200"
5 Press the Up Arrow as needed to select the desired parameter e g up four times for 0204
6 Press ENTER to display current value
7 Press Up and Down arrows to change value e g up until value shows "5"
8 Press ENTER to accept changed value and go on to next parameter
9 Press MENU as needed to return to main parameter screen e g "H 0 00"
Public\tech\Technical bulletins\TB318\TB318 Setup Parameters for Automation Direct GS20 Inverter_rev2 odt Page 1 of 2
TB318 Rev2 – Setup Parameters for Automation Direct GS20 Inverter
Parameter settings
Parameter Description Value
P00 02 Restore to default 10 = set parameters to 60 Hz defaults
P00 04 Drive display 7 = motor speed RPM
P00 20 Frequency command source 2 = external analog input
P00 21 Operation command source 1 = external terminals
P00 22 Stop method 0 = decel ramp
1 = free coast
P00 31 Control method 1 = external control terminals
P01 00 Maximum operation frequency Motor maximum RPM
P01 01 Motor base frequency 60 Hz or from motor nameplate
P01 02 Motor rated voltage 230 or 460 VAC or from motor nameplate
P01 10 Output frequency upper limit 599 0
P01 12 Acceleration time 3 0 – 5 0 seconds
P01 13 Deceleration time 3 0 – 5 0 seconds
P02 04 Terminal DI4 function 5 = fault reset
P02 16 Terminal DO1 function 6 = zero speed
P3 00 Source of frequency command 1 = frequency determined by 0 10VDC on AI1
P03 20 Analog Output 3 = output current CNC11 & CNC12 only
P05 01 Motor full load current Motor nameplate Amps
P05 03 Motor rated speed Motor nameplate RPM
P06 01 Overvoltage Stall Prevention 0 disable if braking resistor is installed 380
or 760 VDC enable if no braking resistor
installed
P06 44 STO Latch Selection 1 no latch if STO circuit is used
Notes
If you wish to use the Safe Torque Off STO function as an alternative to interrupting the incoming line power during an
emergency stop condition while maintaining a reliable drive inhibit then wire from the +24V terminal through two independent
poles of a safety relay back to STO1 and STO2
See page 2 16 of the GS20 Drive User Manual for important information regarding the drive's built in RF filtering and the
need to remove the internal RFI jumper when connected to unbalanced power supplies such as center grounded delta
power or when using a phase converter