TB229 Rev1 Delta VFD VE V2 Inverter ATC Settings
Overview
This Techinical Bulletin describes how to set the parameters for the Delta VFD VE series inverter
To program the Delta Inverter programming parameters
Each Delta inverter parameter has 2 set of numbers
Example 01 02 We will call 01 "Group Parameter" and 02 "Parameter Number "
1 Press "PROG"
2 Press the up or down arrow key to select the group parameter
3 Press "PROG"
4 Press the up or down arrow key to select the parameter number
5 Press "PROG" At this time parameter value should be blinking Use arrow key to change the value
6 Press "PROG" again to save parameter values or "MODE" to discard
Continue until all the parameters have been set
ΓΒ
Parameter Settings
ΓΒ
00 02 Parameter Reset ΓΒ 10 for 220V 60Hz then go back and set to 2 to enable group 11
parameters
00 04 Definitions of Multi Function Control 9
00 10 Controls Method 3
00 17 Carrier Frequency Upper Bound 9 KHz
00 20 Source of Master Frequency Command 2
00 21 Source of Operation Command 1
01 00 Maximum Output Frequency 200 Hz 6000rpm
256 HZ 8000 rpm
01 01 1st Output Frequency 60Hz
01 02 1st Output Voltage Setting 220V
01 12 Accel Time 3 to 5 seconds
01 13 Decel Time 3 to 5 seconds set to 3
02 04 Multi Function Input Command MI4 35 Orient Position Control
02 05 Multi Function Input Command MI5 5 Reset
02 11 Multi Functiion Output 1 Relay 1 ΓΒ 11Error Output
02 12 Multi Function Output 2 Relay 2 ΓΒ 39 Position Attained
02 13 Multi Function Output 3ΓΒ M01 ΓΒ 2 Operation Speed Attained
02 14 ΓΒ Multi Function Output 4 M02 ΓΒ 34 Zero Speed
05 00 Motor Auto Tuning ΓΒ 1 Rolling test 2 Static Test
05 01 ΓΒ Full Load Current of Motor 1 ΓΒ AMP Dependent on Motor
05 02 ΓΒ Rated Power of Motor 1 HP Dependent on Motor
05 03 ΓΒ Rated Speed of Motor 1 RPM Dependent on Motor
05 11 Frequency for Y connection/Delta connection switch 65 sets the change over RPM to 2000
10 00 Encoder Pulses ΓΒ 1024 Dependent on Encoder
10 01 Encoder Input Type Setting 1 or 2 depending on Count direction
10 08 ASR 1/ Switch Frequency 100 Hz
10 19 Position Control Point Orientation Point In Encoder countsΓΒ *
10 20 Range for PG PositionΓΒ ΓΒ 15 counts
10 22 Gain of Zero Speed 0 1 sec
Setting Orient Position Parameter 10 19
Orient card model EMV PG01L
Parameter 10 19 tells the inverter where to position the spindle via encoder counts to orient for use with a ATC To determine the
correct encoder counts please follow the following steps
1 Home the machine
2 To locate the index pulse rotate the spindle one revolution by hand
3 For Umbrella type bring the carousel in with M80 make sure holding down Aux12 For swing arm type bring the arm in with
M13 make sure holding Aux12
4 Slowly jog the Z Axis down and rotate the spindle by hand until the "half key" is lined up with the notch in the ATC
5 At the inverter Press Mode until the "U" led lights up
6 Record this number and enter in Parameter 10 19
Auto Tuning Procedures
1 Static Tuning only Make sure parameter 05 00 is 2
2 Make sure all power wiring is correct
3 Enter the motor rated voltage in parameter 01 02 and the frequency in parameter 01 01
4 Set paremeter 05 00 to XXX then press RUN on the digitial keypad for auto tuning This takes about 2 minutes
5 After auto tuning is complete verify the following parameters have been updated Parameter 05 02 05 06 to 05 12 If not rerun
Autotune
Note
Multi Function I/Os on the inverter should be in "sink"
mode There is a jumper on the board behind the orientation card
If PU mode is locked please follow the following steps below to unlock it
1 P00 02 = 2
2 P00 02 = 5577
3 P11 08 = 8
Document History
Rev1 Created on 2010 03 10
by #240