TB209 Rev1 Setup Parameters for Automation Direct GS2 Inverter
Objective
The purpose of this document is to provide the information needed to correctly setup the Automation Direct GS2 inverter for a Centroid
CNC control
Automation Direct GS2 Inverter Settings
Parameter No Value Units Description
0 00 Depends on motor Volts Motor Nameplate Voltage
0 01 Depends on motor Amps Motor Nameplate Amps
0 03 Depends on motor Base RPM RPM Motor Nameplate RPM
0 04 Must be set with tachometer to match max spindle speed RPM Motor Maximum RPM
1 00 00 = Ramp to a stop  Stopping Method
1 01 3 range = 0 1 to 600 seconds sec Acceleration Time
1 02 3 range = 0 1 to 600 seconds sec Decceleration Time
3 00 01 = External Control Terminals  Control Method
3 03 02 = External Reset  DI4 Multi Function Input
4 00 02 = Frequency determined by 0 10VDC on AI l  Source of Freqency Command
8 00 1 = Motor Speed RPM Â Drive Display
9 08 Â Â Set to 99 to restore parameters to factory default
All other parameters are set to factory defaults  Â
Wiring connections
L1 L2 L3 3 phase power in
DI1 Forward run
DI2 Reverse run
DI4 Fault reset
DCM Input common
AI Master speed frequency reference 0 10vdc
ACM Frequency reference common
R2O Fault output normally open
R2 Fault output common
T1 T2 T3 Motor voltage out
B1 B2 Braking resistor up to 15hp
Document History
Rev1 Created on 2007 06 04
by #240